Search
Search

Terasaki

Terasaki TemPower 2 AR ACB Body AR3 85kA 3200A 3P Non Auto with Motor 240V AC

Item No. ARB3323NAMSTD
Product Range: TemPower 2 Standard
Component Type (ETIM Class)
Power switching circuit breaker
Electrical
Rated current In3200 A
Number of poles3
Max. rated operation voltage Ue AC690 V
Rated ultimate short-circuit breaking capacity lcu at 415 V, 50 Hz85 kA
Rated service short-circuit breaking capacity lcs at 415 V, 50 Hz85 kA
Type of protection trip unitNon auto-switch
Frame size rating3200 A
Rated frequency50-60 Hz
Rated insulation voltage Ui1000 V
Construction
Air circuit breaker (withdrawable)Yes
Mechanical
Mechanical life (service cycles)10000 cycles
Max. vibration acceleration0.7 m/s²
Dimensions
Height490 mm
Width460 mm
Built-in depth385 mm
Weight80 kg
Environment
Pollution degree3
Rated surrounding temperature without derating50 °C
Rated temperature-5-60 °C
Maximum operating temperature60 °C
Allowable relative humidity45-85 %
Max. altitude before derating2000 m